date


Feb 10, 11 2024

dome closed all day. good comparison for subsequent days



Feb 12 2024

dome slit opened 1547 UT
vent is blowing outwards

all four vents opened, slit ~10% (by eyeball), extraction fan VFD at 50Hz (oft mis-characterized as "percent") if you wish to check your telemetry.  I will be working on deciphering the extraction fan VFD modbus command structures this afternoon, so fan speed will probably be changing quite a bit

Air temp dropped 5C upon opening the slit. 


Tests for Feb 13: 

1) roll telescope to horizon for storage
2) find biggest fan and blow upwards along dome edge towards slit
3) leave other lower vents closed. We're just circulating air from lower level with vent fan on
4) daytime venting



Feb 13 20240900 local - Plan is to roll telescope over to low elevation to keep M2 from baking, point telescope N at low elevation, and dome slit S cracked open. Lower vent open and fan at full speed, exhausting through vent. 
looking at choronagraf this seems to be working really well. 














Feb 12, 2024
Goal is to do some thermal management tests with Aux Tel. 
Fritz says dome shutter open fraction and orientation are accessible in EFD and chronograf. 

Added dome shutter open fraction and orientation to IQ Trial panel in coronagraf
Analysis tasks: compare dome status and vent fan speed to temperature behavior for Feb 12 and Feb 13